Shake table tests for the seismic fragility evaluation of hospital rooms
Authors:E Cosenza  L Di Sarno  G Maddaloni  G Magliulo  C Petrone  A Prota
Institution:1. Department of Structures for Engineering and Architecture, University of Naples Federico II, Italy;2. Department of Engineering, University of Sannio, Italy;3. Department of Engineering, University of Naples Parthenope, Italy
Abstract:Health care facilities may undergo severe and widespread damage that impairs the functionality of the system when it is stricken by an earthquake. Such detrimental response is emphasized either for the hospital buildings designed primarily for gravity loads or without employing base isolation/supplemental damping systems. Moreover, these buildings need to warrant operability especially in the aftermath of moderate‐to‐severe earthquake ground motions. The provisions implemented in the new seismic codes allow obtaining adequate seismic performance for the hospital structural components; nevertheless, they do not provide definite yet reliable rules to design and protect the building contents. To date, very few experimental tests have been carried out on hospital buildings equipped with nonstructural components as well as building contents. The present paper is aimed at establishing the limit states for a typical health care room and deriving empirical fragility curves by considering a systemic approach. Toward this aim, a full scale three‐dimensional model of an examination (out patients consultation) room is constructed and tested dynamically by using the shaking table facility of the University of Naples, Italy. The sample room contains a number of typical medical components, which are either directly connected to the panel boards of the perimeter walls or behave as simple freestanding elements. The outcomes of the comprehensive shaking table tests carried out on the examination room have been utilized to derive fragility curves based on a systemic approach. Copyright © 2014 John Wiley & Sons, Ltd.
Keywords:hospital building contents  nonstructural components  shake table test  seismic fragility  fragility curve
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号