Research on single hole heat transfer power of ground source heat pump system
Authors:ZHAO Fang-hua
Institution:1The Third Party of Hydrogeology and Engineering Geology, Hebei Provincial Bureau of Geology and Mineral Investigation, Hengshui 053000, China.
Abstract:In this paper, the single hole heat transfer power of the ground source heat pump system in Hengshui is compared with data gained from thermal response test. The results show that maximum monitoring data of heat transfer power per meter in summer is 97.1% of the test data, and the average value accounts for 81.8%. The per meter heat power data through on-site thermal response test can provide references for designing engineering project and optimizing ground source heat pump system as these data do not vary greatly from the actual monitoring data.
Keywords:Ground source heat pump  Monitoring  Heat transfer power  Thermal response test
本文献已被 CNKI 等数据库收录!
点击此处可从《》浏览原始摘要信息