埋地金属导体对接地系统电阻测试影响试验分析
引用本文:覃彬全,郭在华,陈佳祺,吴刚,糜翔.埋地金属导体对接地系统电阻测试影响试验分析[J].气象科技,2021,49(4):662-670.
作者姓名:覃彬全  郭在华  陈佳祺  吴刚  糜翔
作者单位:重庆市气象安全技术中心,重庆 401147;2 成都信息工程大学,成都 610225;3 中国气象局大气探测重点开放试验室,成都 610225;重庆市沙坪坝区气象局,重庆 400030
基金项目:重庆市技术创新与应用示范项目“爆炸危险场所雷电防护关键技术研究”(项目编号:cstc2018jscx)和重庆市气象局开放式研究基金项目“复杂地质条件下雷电流入地散流机理和腐蚀效应研究”(项目编号:kfjj 201401)资助
摘    要:搭建试验地网研究土壤中金属导体对接地电阻的影响。通过埋设不同形状金属导体,改变金属导体埋设深度、与试验地网相对距离,在不同点位测量试验地网接地电阻值。分析试验数据发现,埋地金属导体导致接地电阻测量值偏小,其中环形金属导体对接地电阻测量值影响最大,一形金属导体对接地电阻测量值影响最小;金属导体位于测试电压极外侧相比位于内侧时,对接地电阻测量值的影响更大;金属导体位于测试电压极内侧时,不同测试点位接地电阻测量值差异较大,金属导体位于测试电压极外侧时,各点位接地电阻测量值差异不大;金属导体埋设深度对接地电阻测量值影响不明显。

关 键 词:埋地金属导体  接地电阻  测试影响
收稿时间:2020/6/24 0:00:00
修稿时间:2021/1/25 0:00:00

Influence Experiment and Analysis of Buried-Metal Conductor on Resistance Test of Grounding Systems
QIN Binquan,GUO Zaihu,CHENG Jiaqi,WU Gang,MI Xiang.Influence Experiment and Analysis of Buried-Metal Conductor on Resistance Test of Grounding Systems[J].Meteorological Science and Technology,2021,49(4):662-670.
Authors:QIN Binquan  GUO Zaihu  CHENG Jiaqi  WU Gang  MI Xiang
Abstract:The influence of a metal conductor in soil on ground resistance is studied by setting up the experimental ground grid. By embedding different shape metal conductors, changing the buried depth of metal conductors and the relative distance from the test grounding grid, the grounding resistance of the test grounding grid was measured at different points. Analysis of test data shows that the buried metal conductor leads to the smaller measured value of grounding resistance, among which the sguare shaped metal conductor has the greatest influence on the measured value of grounding resistance, and the line shaped metal conductor has the least influence on the measured value. When the metal conductor is located outside the test voltage pole, the influence on the measured value of grounding resistance is greater than that on the inside. When the metal conductor is located inside the test voltage pole, the measured value of grounding resistance at different test points is quite different. When the metal conductor is located outside the test voltage pole, the measured value of grounding resistance at each point has little difference. The buried depth of a metal conductor has no obvious influence on the measured value of grounding resistance.
Keywords:buried metal conductor  grounding resistance  test influence